Setup Variables - Power ConsumptionWaste Water Evaporation Water Treatment Water Mister System

Evaporator Power Consumption

The following is actual loaded fan operation data collected by AC Electric at our request to determine actual power consumption. This test utilized a chart recorder and the following summary is from information taken from that chart recorder.

Listed below is record 51 as an average record.

AMP KW POWER FACTOR VOLT KVA CODE EFFICIENCY @ OPERATING 23.49 10.45 .99 450 G 94.2

USEFUL FORMULAS

FORMULAS FOR ELECTRICAL CIRCUITS

Listed below is record 51 as an average record.

 AMP   KW   POWER FACTOR  VOLT   KVA CODE  EFFICIENCY @ OPERATING
  23.49   10.45    .99   450   94.2

USEFUL FORMULAS

FORMULAS FOR ELECTRICAL CIRCUITS

TO FIND DIRECT CURRENT SINGLE PHASE THREE PHASE
AMPERES Watts/volts Watts/volts x Power factor Watts/1.732 x Volts x
Power factor
VOLT-AMPERES    ----------- Volts x Amperes 1.732 x Volts x Amperes
WATTS Volts x Amperes Volts x amperes x power factor 1.732 x Volts x Amperes x
power factor

  FORMULAS FOR ELECTRIC MOTORS

TO FIND DIRECT CURRENT SINGLE PHASE THREE PHASE
HORSEPOWER E x I x EFF/746 E x I x EFF x PF/746 1.732 x E x I Xeff x PF / 746
CURRENT 746 x HP/E Xeff 746 x HP/ E x EFF x PF 746 x HP/ 1.732 x E x EFF XPF
EFFICIENCY 746 X hp/E x I 746 x HP/E x I x PF 746 x HP/1.732 x E X I XPF
POWER FACTOR ---------- Input watts/ E x I Input Watts/1.732 x E x I

E = Volts                                              I = Amperes

EFF = Efficiency (decimal)                    PF = Power Factor (decimal)

HP = Horsepower

Utilizing these formulas allow us to determine the operational cost of running our motor which has a plated horse power of 40 but actually operates at 23 horsepower as you shown on the following page, using our chart recorder figures to do the calculations.

Click Here for more information on the Power Consumption of the Turbomist S30 Evaporator